Skip to main content

Alarm Interface Module

Item Number: 3006204193

Alarm interface module with software for IPTV

The Alarm Interface Module is used to provide a mute (or turn-off) TV option and to send a dynamic message to the screen during PA/GA.

  • 35mm DIN rail or direct surface mount
  • 10/100 RJ45 Ethernet port
  • 12x Terminals for connecting Alarm contacts, e.g.:
    • General alarm
    • Abandon
    • Manual
    • Fire Crew
    • Fire ALL
    • Other alarm
  • When input contact is closed, every alarm input sends different UDP command to network server
    • For example: "ALARM 1 ON", "ALARM 1 OFF", etc.
  • Commands can be sent every 2ms (to have enough time for network to react)
  • Customizable UDP commands up to 38 Characters, e.g. command could be "/ par1 / par2 - ALARM01 STATUS ACTIVE"
  • Commands can be sent constantly during closed contact to have fail-safe function
  • Priorities between alarms (1st General, 2nd Abandon, etc.)
  • Web interface with all information
    • Unit IP address, subnet mask, default gateway, Local (UDP) port
    • Remote IP address, Remote (UDP) port
    • On/Off commands for each alarm
  • Fully web customizable
    • Change unit IP address
    • Change unit subnet mask
    • Change default gateway
    • Change unit local (receiving) port
    • Set remote IP address
    • Set remote (destination) port
    • Customize each alarm command (every alarm ON and OFF commands)

 

PHYSICAL AND POWER
Mounting 35mm DIN rail or wall/desk mounting
Weight 0,2 Kg
Dimension (W x H x D) 88 x 90 x 58 mm
IP / NEMA Rating IP-20
Power supply +24VDC (18-36VDC), Power reverse polarity protection
Max. Current consumption 70mA @24VDC (1,68 Watt)
ENVIRONMENT
Operating Temperature -0°C to +40°C
Storage Temperature -40 to 85°C
Humidity (no condensing) 95% RH
INPUTS / OUTPUTS
10/100 RJ45 Ethernet port
Power input 18-36 VDC
6x input contacts (normal open contacts)
1x relay contact
Date Name Category Size Document