Skip to main content

UPS-NRT-2700-230T

Item Number: 2970000044

Online UPS with extra battery 2700W/30min, 230VAC. Tower mount.

  • 2x Tower mounting brackets
  • 8x Vibration dampers
  • 2x Extra battery
  • Runtime: 2700W / 30 minutes
  • DNV-GL Type Approved

 

    The marine industry calls for reliable equipment which is able to supply applications operating in harsh environments. In such a context, power outages cause extremely serious problems to critical equipment for the navigation system, and communication and engine controls, which leads to costs increasing. In line with the company’s commitment to developing innovative solutions to ensure availability, improve energy efficiency and reduce costs, Zenitel has introduced high-performance UPS, DNV GL standard certified.

    • Online double conversion technology with a sinusoidal waveform.
    • Permanent regulation of output voltage and frequency.
    • Wide tolerance of the input voltage.
    • No configuration is necessary on the first startup
    • Installation inside standard 19“ rack cabinets.
    • Includes extra modular battery

    NRT2-U3300C is the ideal solution for the following:

    • Switching
    • Servers and networking devices
    • VoIP communication systems
    • Structured cabling systems
    • Control systems
    • Video surveillance systems 

    Product variants:

    Item 2970000025, UPS Bracket Mount. Includes:

    • NRT2-U3300C, Online UPS 3300VA 2700W.
    • 2x NRT-B3000 Extra Battery cabinet, Capacity:2700W - 30min,2500W - 40min, 1800W - 60min, 1300W - 90min
    • NRT-FBD: Set of brackets for 2x batteries.
    • NRT-OP-CBL11B
    • NRT-FB: Set of brackets for UPS
    • NRT-VIB2: 8 Vibration dampers

      Option: EMC filter for installation on Bridge - according to the DNV/GL certificate.

      General
      Sn 3300 VA
      Pn 2700 W
      Architecture on-line double conversion VFI with input PFC and automatic bypass
      Input Rated Voltage 230 V (1ph)
      Input Voltage Tolerance 175÷280 V; up to 120 V @70% load
      Input Power factor / THDI > 0.99 / < 5%
      Output Rated Voltage 230 V (1ph)
      Output Voltage Tolerance selectable 200/208/220/240 V
      Output Frequency Tolerance ± 2% (± 0.05 Hz in battery mode)
      Output Power factor 0.9 @ 3000 VA
      Efficiency up to 93% online mode
      Overload capability up to 105% continuously; 125% for 3 min; 150% for 30 s
      UPS Cabinet, Dimensions W x D x H 89 x 608 x 440 mm (2U)
      UPS Cabinet, Weight 30 kg
      External Battery Module, Dimensions W x D x H 89 x 608 x 440 mm (2U)
      External Battery Module, Weight 43 kg
      2x NRT-B3000 Battery Estimated time: 2700W - 30min, 2500W - 40min, 1800W - 60min, 1300W - 90min
      IP Rating IP20
      PRODUCT VARIANTS
      2970000012 Online UPS with extra batt.- 1000W/30min rack mount 230VAC
      2970000013 Online UPS with extra batt.- 1500W/30min rack mount 230VAC
      2970000014 Online UPS with extra batt.- 3500W/30min rack mount 230VAC
      2970000021 Online UPS with extra batt.- 600W/30min incl.bracket 230VAC
      2970000022 Online UPS with extra batt.- 1000W/30min incl.bracket 230VAC
      2970000023 Online UPS with extra batt.- 1500W/30min incl.bracket 230VAC
      2970000024 Online UPS with extra batt.- 3500W/30min incl.bracket 230VAC
      Accessories
      2970000200 NRT-OP-REL, I/O card for Netys RT
      NRT-OP-RAIL 19" Extra mounting rail for all UPS

      Date Name Category Size Document
      12.10.2023 2970000044 - UPS-NRT-2700-230T - Dimensional Drawing CAD 2D 834.25 KB Login to download
      11.09.2023 MD-SDoC-2970000025-IHM-8003-46266-154328.xlsx Declaration 72.19 KB Login to download
      10.12.2020 NRT2_DNV-GL.pdf 73.74 KB Download
      9.11.2020 HR9-12.pdf 301.52 KB Download
      9.11.2020 COD_17_89848_-_REACH_COMPLIANCE_DECLARATION_EN.PDF 283.69 KB Download